8A
PROGRAMMATION
DES DIPSWITCHES
SETTING THE CONFIGURATION
DIPSWITCHES
CONFIGURATION PAR DEFAUTDEFAULT CONFIGURATION
- Fan always on.
- Temperature control (ON/OFF) on the water
valve/valves.
- T3 disabled.
Note: probe T3 (cut-out thermostat) is already
fitted; to enable the operation of the probe,
set dipswitch 2 to OFF.
- Ventilation continue.
-
Thermostatation (ON/OFF) de la (des)
vanne(s) eau.
- T3 désactivée.
Note: la sonde T3 (limitation basse) est montée;
si on veut en activer le fonctionnement
mettre le Dip 2 sur OFF.
8
IMPOSTAZIONE
DIP DI CONFIGURAZIONE
CONFIGURAZIONE DI DEFAULT
- Ventilazione continua.
-
Termostatazione (ON/OFF) delle/a valvole/a
acqua.
- T3 disattivata.
Nota: la sonda T3 (di minima temperatura) è
montata; se si vuole attivarne il funziona-
mento, porre il Dip 2 in OFF.
x = Non importante per la specifica funzione
Not important for the specific function
Pas important pour la fonction spécifique
* = Configurazione di default
Default configuration
Configuration par défaut
Configurazione raCComandata nel Caso non Vi sia Presenza delle ValVole aCQua
Configuration reCommended if the WATER VALVES ARE NOT USED
Configuration reCommandée sil N’Y A PAS de VANNES D’EAU
r
aggiunto il Valore di temPeratura imPostato,
il motoVentilatore Viene Portato in off senza alCuna Post-Ventilazione.
onCe the set temPerature has been reaChed, the motor-driVen fan is
switChed
off without any Post-Ventilation.
lorsQue la temPérature Programmée est atteinte, le Ventilateur se
met
sur off sans auCune Post-Ventilation.
Impianto a 4 tubi
1 2 3 4 5 6 7 8
ON
CONFIGURAZIONE
Posizione Switches
Impianto a 2 tubi
Esclusione T3
Sonda di minima T3 attiva
Senza telecomando
Con telecomando
Ventilazione continua
Autofan in raffreddamento
Autofan in riscaldamento
Autofan sempre
Senza valvole
(ON-OFF sul ventilatore)
Con post-ventilazione
3 minuti
Senza post-ventilazione
Unità Master
Unità Slave
x x x x x x x
OFF * x x x x x x x
x ON * x x x x x x
x OFF x x x x x x
x x ON x x x x x
x x OFF * x x x x x
x x x ON * x x x x
x x x OFF ON OFF * x x
x x x OFF OFF * ON x x
x x x OFF ON ON x x
x x x OFF ON ON ON x
x x x x x x OFF * x
x x x x x x ON x
x x x x x x x ON
x x x x x x x OFF *
4-pipe system
1 2 3 4 5 6 7 8
ON
CONFIGURATION
Switch position
2-pipe system
Disable T3
Enable T3 cut-out thermostat
Without remote control
With remote control
Fan always on
Autofan in cooling
Autofan in heating
Autofan always
Without valves
(ON-OFF on the fan)
With post-ventilation
3 minutes
Without post-ventilation
Master unit
Slave unit
x x x x x x x
OFF * x x x x x x x
x ON * x x x x x x
x OFF x x x x x x
x x ON x x x x x
x x OFF * x x x x x
x x x ON * x x x x
x x x OFF ON OFF * x x
x x x OFF OFF * ON x x
x x x OFF ON ON x x
x x x OFF ON ON ON x
x x x x x x OFF * x
x x x x x x ON x
x x x x x x x ON
x x x x x x x OFF *
Installation 4 tubes
1 2 3 4 5 6 7 8
ON
CONFIGURATION
Position Switches
Installation 2 tubes
Exclusion T3
Sonde de limitation T3 basse
Sans télécommande
Avec télécommande
Ventilation continue
Autofan en refroidissement
Autofan en chauffage
Autofan toujours
Sans vannes
(ON-OFF sur le ventilateur)
Avec post-ventilation
3 minutes
Sans post-ventilation
Unité Maître
Unité Esclave
x x x x x x x
OFF * x x x x x x x
x ON * x x x x x x
x OFF x x x x x x
x x ON x x x x x
x x OFF * x x x x x
x x x ON * x x x x
x x x OFF ON OFF * x x
x x x OFF OFF * ON x x
x x x OFF ON ON x x
x x x OFF ON ON ON x
x x x x x x OFF * x
x x x x x x ON x
x x x x x x x ON
x x x x x x x OFF *