Spigot
for air distribution
MAIN AIR INLET
AIR INTAKE
Two air outlets are provided
on the side of the unit for connection
to separate supply air outlets.
They can be used to supply air from
the fan coil unit to distant areas of a room
or even to a different room.
The total air flow does not change.
The air flow at high speed depending
on the air duct pressure drop is shown
in the tables below.
Note: all air ducts must be insulated
in order to avoid condensation.
Air distribution - Air distribution connection
The cassette is fitted
with inlets for fresh air to be mixed
with return air inside the unit (Fig. 3).
The fresh air flow is limited to 20%
of the total fan coil air flow at medium speed
and 100 m
3
/h for each treated air inlet.
The units feature fresh air inlets
on three corners (no inlets on the fourth corner
because of the condensate pump inside the unit).
The fresh air inlets are designed for the insertion of standard 110 x 55 mm rectangular ducts.
The air duct is connected quickly and easily. After removing the blank and the insulation inside the unit,
the mounting plate is rolled back and the air duct with its V-shaped section
must be pushed into the unit (see Figures below). The duct is then fixed to the mounting plate.
Note: the fresh air must be filtered.
Accessory “Fresh air connection” - Identification CAP - Code 6078005 (see page 14)
AIR DISTRIBUTION
AIR INTAKE
Fresh
air connection
MAIN
AIR INLET
AIR INTAKE
1 2 3 4
Fresh air supply - Fresh air connection