INTAKE GRID AND DISTRIBUTION OF THE AIR
Intake grids, frame and adjustable air distribution louvers on each side, made from ABS.
RSNA version : white ABS, RAL 9003
RSNB version : with intake grid, frame and louvers, choice of one colour only
RSNC version : with intake grid and louvers, choice of one colour, plus white ABS frame RAL 9003
RSND version : with louvers, choice of one colour, while the grid and frame are made from ABS,
RAL 9003
MD-600 version : metal diffuser painted in RAL 9003 white colour with 600x600 dimension to perfectly
fit into the false ceiling standard modules without overlapping parts (800x800 model
is not available).
CASING
Is made from galvanized steel with inside thermal insulation (closed cell polyethelene 10 mm thick) and
outside anti-condensate lining.
CONTROL EQUIPMENT
TL
-
ECM version
It consists of the pump control circuit board and the inverter circuit board.
TL
FAN ASSEMBLY
The fan assembly, which is mounted on anti-vibrating supports, is extremely silent.
The radial fan has been designed to optimise performance, using wing profile blades with a shape that
reduce turbulence, increasing efficiency and reducing noise.
The fans are connected to a BLAC three phase permanent magnet DC brushless electronic motor that
is controlled with current reconstructed according to a sinusoidal wave.
The inverter board that controls the motor operation is powered by 230 Volt, single-phase and, with a
switching system, it generates a three-phase frequency modulated, wave form power supply.
The electric power supply required for the machine is therefore single-phase with voltage of 220 - 240 V
and frequency of 50 - 60 Hz.
HEAT EXCHANGER
Made of copper tubes with bonded aluminium fins for maximum transfer contact.
The batteries are with 2 or 3 rows for 2 pipe models and 2+1 rows for 4 pipe models (the heating row is
on the inside part of the battery).
For 4 pipe systems two versions are available:
TL 1.4T and TL 4.4T supply an higher heating emission;
TL 2.6T, TL 3.6T, TL 5.6T supply an higher cooling emission.
The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminium
may be subject to corrosion.
CONDENSATE COLLECTION TRAY
High density ABS polystyrene foam condensate tray, shaped in order to optimize the air diffusion, fire
retardant rating B2 to DIN 4102.
AIR FILTER
Synthetic washable filter, easily removable.
CONDENSATE PUMP
Float switch centrifugal pump with 650 mm of maximum head, integral to the unit and wired to the control
panel on the outside of the casing.
VALVE SET
Two or three way valves for ON/OFF operation, with pipe mounting kit and thermostatic actuator.
TopLine ECM
Main components
-
ECM
-
MB version
It consists of the MB electronic board (that integrates pump control) and the inverter board.
23