Accessories
TME low temperature cut-out thermostat
Suitable for wall controls only (not infra-red remote control). To be fitted between the coil fins;
when connecting the control, the TME probe cable must be separated from the power supply wires.
To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI.
Change-Over CH 15-25
Suitable for wall controls only (not for infra-red remote control).
Automatic summer/winter switch to be installed
in contact with the water circuit (for 2-tube installations only).
To be used with the following controls:
TMO-T, TMO-T-AU, TMO-DI.
Fresh air connection
See page 13.
Fresh air kit
This is used to introduce primary air into the environment directly through the
diffuser. The kit includes a flow separator to be fitted inside the cassette, and
a circular fitting for connection to the flexible system ducting. The flow of air is
sent directly to just one of the outlet louvers, without passing through the coil.
The air flow of fresh air introduced into the environment depend on the inlet
static pressure.
The diameter of the fitting
is 150 mm for TL 0 - 1 - 2 - 3
and 180 mm for TL 4 - 5 - 6.
Units with remote electric board
On request the TopLine cassettes are available with electric control panel reachable from below and with the electric
board that can be placed in a remote position. In this case the units are supplied with an electronic connecting control
panel, fitted to the bottom side on the 4 smallest sizes and to the
lateral side on the 3 biggest sizes.
The electronic control panel is connected to the fan motor, to the
condensate pump and to the condensate level control. A 6 m wire
is also supplied with integral plug-in connections to connect the unit
with the remote electric board that can be installed in a suitable and
comfortable position, where the power and system connections can
be made easily.
This feature is not available for units with electric resistance or infra-
red remote control.
Identification TME
Code 3021091
the water temperature is lower than 38°C
and it starts the fan when is higher than 42°C.
It stops the fan when
Identification CH 15-25
Code 9053049
Identification CAP
Code 6078005
PRT 600 PRT 800
9079230 9079231
Model
Code
Identification
TL 0-1-2-3 TL 4-5-6
80 3 160 3
120 8 200 8
160 15 300 15
200 25 400 25
240 36 500 36
Correlation between
flow-rate/static pressure
m /h
3
Pa
m /h
Pa
3
TL 0-1-2-3 TL 4-5-6
19