The MB power electronic board,
mounted as per standard on the TL
and TL
different functions and adjustment modes,
in order to meet the installation requirements
.
These modes are selected
by setting the configuration dip switches
on the board.
MB power electronic board
MB controls
TopLine /TopLine ECM
• 2/4 pipe system.
• Fan ON/OFF thermostatic control.
• Valve ON/OFF thermostatic control
and continuous ventilation.
• Valve and simultaneous ventilation ON/OFF
thermostatic control.
• Fan operation control
depending on the coil temperature (cut-out T3 probe fitted), which can be activated
only in heating mode or heating and cooling mode.
• Automatic switch of the operating mode
by means of T2 water probe (optional) applied on the 2 pipe system.
• Seasonal switch by means of remote contact.
• ON/OFF of the fan coil by means of the remote contact
(window or clock contact).
• Electric heater control.
By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°C
and started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside the
coil exceeds 22°C and starts when it drops below 18°C.
The following connections are located on the power board:
• Receiver for infra-red remote control.
• T-MB wall mounted control.
• RS 485 serial connection to manage several fan coils in Master/Slave configuration
or to create a supervisory network.
-MB
- ECM-MB versions, is set to carry out