Sabiana IRC board-remote c Manual de usuario Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 25
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
53
RED
BROWN
RED
BLACK
MV
Mo
MVB
iV
io
CRC / CRR
3021091
Model
VeRsion
Code
MV
Mo
MVB
iV
io
CRC / CRR
9053048
Model
VeRsion
Code
MV
Mo
MVB
iV
io
CRC / CRR
9053049
Model
VeRsion
Code
To be fitted between the coil fins; when connecting the control,
the TME probe cable must be separated from the power supply wires.
To be used with the following controls:
CB-C, CB-AU, TMO-T, TMO-T-AU, TMO-DI and corresponding IAQ controls.
It stops the fan when
the
water temperature is lower than 38°C
and it starts the fan when is higher than 42°C.
TME low temperature cut-out thermostat
Electronic control accessories
for CRC / CRR units
To be installed in contact with the hot water circuit.
To eliminate cold air blow.
Installed by the installing engineer.
To be used with the following controls:
CB, CB-T, CB-IAQ, MO-3V, CR-T, MO-3V-IAQ.
For units working on heating only.
It stops the fan when
the water temperature is lower than 30°C
and it starts the fan when is higher than 38°C.
TMM low temperature cut-out thermostat
Automatic summer/winter switch
to be installed in contact with the water circuit.
For 2-tube installations only
(not to be used with 2 way valve).
To be used with the following controls:
CB-C, CB-AU, TMO-T, TMO-T-AU, TMO-DI.
Change-Over CH 15-25
Vista de pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 24 25

Comentarios a estos manuales

Sin comentarios