• Fan absorption • Water pressure drop • Sound power
• Heating emission (2 pipe units) at the following conditions:
- Entering water temperature +50°C
- Entering air temperature +20°C
- Water flow rate as for the cooling conditions
• Heating emission (4 pipe units) at the following conditions:
- Water temperature +70°C E.W.T. +60°C L.W.T.
- Entering air temperature +20°C
• Cooling total emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T.
- Entering air temperature +27°C dry bulb +19°C wet bulb
• Cooling sensible emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T.
- Entering air temperature +27°C dry bulb +19°C wet bulb
Sabiana take part to the Eurovent program of fan coil performance certification.
The official figures are published in the web site
www.eurovent-certification.com and in the web site www.certiflash.com.
The tested performances are:
THE ULTRA QUIET FAN COIL
In line with innovative trends and modern industrial design, the
Carisma fan coil range meets today’s demanding requirements
of performance, size, acoustics, low energy, ease of installation
and maintenance. The Carisma fan coil unit has been designed
around a platform of models, versions and accessories, all
of which have been independently tested and certified by
Eurovent.
Designed around 5 different versions, the extensive range
includes wall and ceiling mounted units, exposed or concealed
with either tangential or centrifugal fan options, delivering one
of the most versatile ranges of fan coils on the market today.
All CRC fan coils with centrifugal fans are equipped with electric
motors which dramatically reduce electrical consumption of
up to 40% comparative to previous models, with 6 speed
motors as standard offering greater flexibility in the selection
of products.
New market trends have also led to an extension of the four
pipe model which now has a two row LTHW battery giving
improved outputs at lower flow and return temperatures.
As a special option, the Carisma range can be fitted with a
patented electronic filter featuring a class D rating according
to Standard UNI 11254, with similar performances to the initial
ones of a traditional mechanical filter featuring a class F9 rating
according to Standard UNI EN 779.
A full range of adjustment and control devices is available
including the FREE innovative patented
wireless system, for rapidly obtaining
correct environmental temperature and
with an investment proportional to
performances, comfort and desired
measurement precision.
The Carisma model is complemented with
a full range of accessories: various types
of adjustment valves, sturdy support feet,
rear covering panel for glass installation,
additional electric heater, auxiliary
condensate pump, fresh air intake
louver, air inlet/outlet diffusers for fitted
installations.
The CRR range with tangential fan combines
a reduced dimension (183mm depth) with a modern
aesthetic that perfectly suit with any kind of furnishing, while
maintaining great performances in terms of sound and consumption.
CONTENTS
• Construction (CRC) Page 4
• Models
(CRC) Page 5
• Dimensions,
Weight, Water content
(CRC) Page 6
• EUROVENT certification
(CRC) Page 10
• Operation limits
(CRC) Page 13
• Emission tables
(CRC) Page 14
• Correction factors table
(CRC) Page 24
• Water pressure drop
(CRC) Page 25
• Construction
(CRR) Page 26
• Dimensions,
Weight, Water content
(CRR) Page 27
• EUROVENT certification
(CRR) Page 28
• Operation limits
(CRR) Page 28
• Emission tables
(CRR) Page 29
• Water pressure drop
(CRR) Page 31
• Accessories for
CRC/CRR units Page 32
• CRYSTALL electrostatic filter
(CRC) Page 39
• Controls for
CRC/CRR units Page 46
• FreeSabiana wireless control system
for
CRC/CRR units Page 54
•
CRC/CRR units
with IRC electronic board
Page 56
• Maxinet management system
for a network of
CRC/CRR units Page 60