CRR units with IRC electronic board
IRC electronic board
The electronic board, fitted inside the electrical panel, can manage different control modes so as to best satisfy the
requirements of the installation. These modes are selected by suitably positioning the configuration dipswitches,
which define the following main functions:
2 pipe / 4 pipe system
Operation without / with remote control
Continuous ventilation
Close valve
and stop fan in cooling mode (autofan function)
Close valve
and stop fan in heating mode (autofan function)
Close valve and stop fan
in both cooling and heating mode (autofan function)
The autofan function allows the simultaneous ON/OFF control of the water
valve and the fan, while at the same time optimising the operation of the unit.
When reaching the set point, the controller closes the water valve (valve OFF)
and only 3 minutes later stops the fan, so as to correctly compensate for the valve
closing time. To prevent the air probe from measuring an incorrect temperature, when the
fan is OFF the controller runs a number of fan ON cycles to annul the effect of any stratification
of the air in the room.
In two pipe systems, a water probe (T2 accessory) can be installed on
the supply pipe to the unit upstream of the water valve. Based on
the temperature read in this section of the pipe, the device will
select either cooling or heating operation.
The electronic board also features a contact for connection to a
window switch or remote enabling signal. When the contact is
closed, the unit can operate, when the contact is open, the unit
stops. The same contact can be used for starting and stopping the
unit from an external timer or any other remote switching device.
In addition, a series of units can be switched ON or OFF at the same
time, by using a flip-flop switch connected to the terminals present on the
board.
Sensors that require a 12 Volt power supply, for
example occupancy sensors, can be connected to
other terminals on the electronic board and then to
the ON/OFF contacts. The board is able to power
external sensors with a maximum current of 60 mA.
irc
eLecTronic board
insTaLLaTion exampLe
wiTh
infra-red remoTe conTroL